T9310-02 ICS Triplex modular

T9310-02

We will let time prove that your choice is correct!

We will use our sincere service to exchange 200% of your satisfaction

High quality and low price spot goods to provide your satisfaction is our goal

For customers who cooperate with us for the first time, we can provide qualification and scanning copy of bills issued by recent sales for inquiry before ordering.

After sales problems: Follow the standards of the manufacturer of the brand to ensure after-sales service and one-year warranty for all products

Description

Manufacturer : ICS Triplex

Product No. : T9310-02

System Supply Voltage Range : 20 to 32V dc

Number of Inputs : 40 Channels

User Defined Thresholds : 4-off

Input Current Range : 0-22mA

Input Voltage Range : 0-6 Vdc

Sample Update Time : 0.5ms

Resolution : 3.9uA (1/256mA)

Safety Accuracy : +/- 1% of full scale

(default threshold above which 0x70nn series slice discrepancy faults are raised)

Calibration Accuracy : 0.03%

Recommended input channel calibration check

interval : 2 years

Circuit Type : Fault tolerant, fully triplicated with optional line monitoring

Fusing : None, external if required

Intrinsic Safety External barrier

Sequence of Events

Event Resolution : 1ms

Time-stamp Accuracy : ±0.5 ms

Field Common Isolation

Sustained Working : ±250V dc

Maximum Withstanding : ±2.5kV dc

Channel to Channel Crosstalk : -40 to –60 dB

Power Consumption : 15 – 18W

Self-Test Interval : 2 minutes

Operating Temperature : -5°C to 60°C (23°F to 140°F)

Non-operating Temperature : -25°C to 70°C (-13°F to 158°F)

Temperature change : 0.5ºC/min

Operating Humidity : 10 – 95% RH non-condensing

Environmental Specifications : Refer to Document 552517

Dimensions

Height : 266mm (10.5ins)

Width : 31mm (1.2ins)

Depth : 303mm (12ins)

Weight : 1.149kg (2.5lbs)

Real Time Clock Resolution : 100µSec

Shipping Weight : 2 Kg