Model TRICONEX 3664
Nominal voltage digital output module 24 VDC
Type Dual DO, serial (recommended for de-energized trip control programs)
Output signal 32, common
Voltage range 16-30 VDC
Maximum voltage 36 VDC
Voltage drop < 1.5 VDC, typical
Power Module Load < 10W
Rated current, max 2A per point each
10 ms surge 10A
Load leakage max. 2 mA
Fuses (on field terminals) n/a – self-protection
Point isolation 1,500 VDC minimum
Diagnostic Lights
on or off state
module status
live alert
1 per point
PASS, FAULT, ACTIVE
LOAD/FUSE
Load Alert, Output Stuck 3664 – Stuck Point, All Other Command Status – On or Off
3674 – Stuck point, all other commands off (power off)
Load Alert, Output Stuck Off 3664 and 3674 – Stuck-Off Point, All Other Command Status – On or Off
color code dark blue